SmartGen丨Application of Three Power Automatic Switching System-Smartgen,Genset Controller,Generator Controller,ATS Controller,panel manufactory,ats manufaction,battery charger manufactory,battery charger,genset control panel,engine heater,engine controller,marine engine control module,marine diesel control module,boat engine controller,marine engine control module,marine engine controller 






SmartGen丨Application of Three Power Automatic Switching System

2020-12-18



With the rapid development of industry, people have higher and higher requirements for power supply reliability. In some important occasions, dual-power switching cannot meet the requirements, so it is necessary that reliable switching between the three powers to ensure the power supply continuity. As the core control part of three-power switching, three-power ATS controller is indispensable and plays a vital role. In order to meet the switching scheme of different switches and applications, SmartGen has developed HAT832 and HAT833 three-power ATS controller to meet the market demand.


1.jpg


HAT832 is used for Three Power switching system consisting of two ATS switches, which can be applied to Mains-Mains-Gen, Mains-Gen-Gen and other system types.


  • Can be used for various PC-level switches;

  • Collect and display 3-way 3-phase voltage, frequency and phase sequence;

  • Collect and display load active power, reactive power, apparent power, power factor and current;

  • S1/S2/S3 priority arbitrary setting;

  • Power system type can set as Mains-Mains-Mains, Mains-Mains-Gen, Mains-Gen-Gen;

  • Voltage transformer ratio function;

  • Black box function, which can cycle record 5 pieces of log and each log contains 60 groups of data including switch status detailed data of 50s before and 10s after switchover;

  • Can control two gensets to realize cycle run, master-slave run and balanced run;

  • Genset scheduled run/scheduled not run function that can set as run once a day/week/month.


2.jpg

HAT832 Project Application (S1 Mains-S2 Gen-S3 Gen)


HAT833 is used for Three Power switching system consisting of three ACB switches


  • Collect and display 3-way 3-phase voltage, frequency and phase sequence;

  • Collect and display load active power, reactive power, apparent power, power factor and current;

  • S1/S2/S3 priority arbitrary setting;

  • S1/S2/S3 master input, highest switching priority when input port is active;

  • Input ports forced manual mode and auto mode;

  • Auto transfer/restore input, auto transfer/restore when active, auto transfer, non-restore when inactive;

  • Elevator control output, output before load outage or switch transfer, is used to control the running elevator to stop at the nearest floor until the switch transfer is completed;

  • Closed output of 3-way ACB switches;

  • Switch is transferring, output during the switch transfer process;

  • Voltage transformer ratio function.


3.jpg

HAT833 Project Application (S1 Mains-S2 Mains-S3 Gen)


www.smartgen.cn

5.jpg





SmartGen Internet +



Cloud Monitoring Platform

Control your genset at any time


English WeChat Service

Scan QR code to get information in time


SmartGen Products APP

Get products information in real time


Smartgen Media

Acquire trends of SmartGen at any time











WEB:中文·繁体·English·Taobao·AliExpress

TEL:0086-371-67988888/67981888  FAX:0086-371-67992952

ADD:No.28 Jinsuo Road, Zhengzhou City, Henan Province, China

E-MAIL:sales@smartgen.cn

Business Partner:Woodward

Copyright© Since 1998 SmartGen




Smartgen Media:Facebook . Twitter . Linkedin . Odnoklassniki . VK . Blogger . Wordpress . Tumblr . Ameba . Naver . YouTuBe . Pinterest . Site123 . Nifty . Mix Wixsite . Strikingly . Hatena


HAND-IN-HAND WITH YOU, WIN-WIN IN FUTURE.